Lightning Risk Assessment Calculator | NFC 17-102 |

Lightning Risk Assessment - ARAM
Calculating

ARAM

Lightning Protection Systems

LIGHTNING RISK ASSESSMENT

Protection Level Selection - NFC 17-102 Standard

Structure Dimensions
C1 - Environment Coefficient
C2 - Structural Coefficient
Metallic Structure
Common Structure
Flammable Structure
C3 - Content Coefficient
C4 - Structure Occupancy
C5 - Lightning Consequences
Annual Average Thunder Days

ARAM

Lightning Protection Systems

Lightning Risk Assessment

Calculation of Protection Level - NFC 17-102

CALCULATION OF PROTECTION LEVEL
FORMULAS VALUES RESULTS
The Equivalent Collection Area of Structure L=50 Ae=15061.7251
Ae=L×W+6H(L+W)+πH² W=30
(For rectangular fields) H=15
Expended Lightning Frequency Td=30 Nc=0.0423
Ng=0.04Td1.25 Ng=2.8084
Nc=Ng×Ae×C1×10-6 Ae=15061.7251
Accepted Lightning Frequency C1=1 Nd=0.0002
C=C2.C3.C4.C5 C2=0.5
Nd=5.5.10-5/C C3=1
C4=1
C5=5
If Nd ≤ Nc →Optional Protection
Efficiency , E=1-(Nd/Nc)

Efficiency

E= 0.95
0.95 ≤ E < 0.98

Protection Levels

LEVEL I | I
Active | Faraday Cage

Piezoelectric Crystal Active Lightning Conductor Selection Table

Ng ∆T=15μs ∆T=30μs ∆T=45μs ∆T=60μs
H(m) I II III IV
213151820
425303641
532374551
632384652
833394754
1034404956
2035445563
3035455569
6035456075

Selection table for electrostatic active lightning conductor

Ng ∆T=30μs ∆T=45μs ∆T=60μs
H(m) I II III
2192225
4384451
5485563
6485564
8495665
10495766
20505971
30506073
60506080

According to level of Faraday Cage Protection System Criteria

Protection Levels Down conductor distance
I10
II10
III15
IV20

Angle and height level of protection depends α

Protection Level Sphere radius (m) Cage Size
I205x5
II3010x10
III4515x15
IV6020x20